Atalika, TevhidDogan, MustafaDemirci, Turan2024-02-272024-02-2720150378-7796http://hdl.handle.net/11727/11636Identifying inter-area oscillations can be a challenge for interconnected grids. Two identifier algorithms (FBMSWA and TBR-EMD) proposed to detect these oscillations are comparatively tested in this research. FBMSWA is implemented with T-STATCOM to damp out 0.15 Hz low-frequency inter-area oscillation after interconnection Turkey with ENTSO-E. Developed TBR-EMD algorithm has certain achievements, e.g. admissible for real time, handling intermittency problem of EMD, proved by real data. (C) 2015 Elsevier B.V. All rights reserved.enginfo:eu-repo/semantics/closedAccessInter-area oscillationsSTATCOMHilbert-Huang transform (HHT)Empirical mode decomposition (EMD)FFTTarget-based refinementDesign and Implementation of An Identifier System for Inter-Area Power Oscillationsarticle12286950003508336000112-s2.0-849215308711873-2046